AVR-01-K control device back supply
- Customer pickup,
- Courier
- In detail
- TypeEmergency input of the reserve
Assignment:
The control device of AVR-01-K is intended for creation of schemes AVR with two inputs of a power supply, one loading.
Principle of work:
The control device of AVR-01-K controls tension on two inputs of the three-phase alternating current main. If tension within norm, loading is connected to the main input by means of the external switch (the contactor, the time cut-out with the motor drive, etc.) which is managed by the AVR-01-K final-control relay. At accident loading is connected to reserve input of a power supply. At recovery of a power supply on the main input loading switches to it. A power supply of AVR-01-K is carried out from controlled inputs.
Specifications:
Parameter | AVR-01-K |
---|---|
Type of controlled lines: | 4-wire (3x400B+N) |
Supply voltage: | 85-264B |
Number of controlled inputs: | 2 |
Number of final-control relays: | 3 |
Max. current of contacts of the relay: | 16A AC1 |
Max. current of the coil of the contactor: | 3A |
Contacts: | 3x1P (switching) |
Shutdown tension threshold: - lower - upper |
150-180B 240-270B |
Clearing time: - for a lower limit - for an upper limit |
5B 0,3B |
Admissible asymmetry of tension: | 60B |
Time otkl. on asymmetry: | 5 sec. |
Switching time from the basic on reserve input: |
0,3-5sek |
Time incl. the main of input at voltage recovery: |
5 sec. - 10 min. |
Degree of protection: | IP20 |
Operating temperature range: | from-25 to +50 C |
Dimensions: | 105kh65kh90mm |
FUNCTIONAL FEATURES:
1. Control of alternation of phases.
2. Forming of tension of an operational power supply.
3. Asymmetry control.
4. Forming of a signal of start of the generator.
5. Management of contactors and motor drives.
6. Control of position of contactors (motor drives).
7. Availability of entrances of an emergency shutdown of loading.
8. A possibility of work from the external power source.
9. Preservation of working capacity with the voltage range from 24 to 264B.
10. The combined adjustment of upper and lower thresholds of tension.