Fixed Gas Detection Controller MX 15
- Самовывоз,
- Курьер
- Детально
1 channel
Low cost and easy to install
DIN rail mounting
3 built-in discrete relays
For any transmitters/detectors
Continuous self-checking
Overview
Designed for use in boiler rooms and parking garages, the new MX 15 controller provides the most cost effective solution for the continuous monitoring of toxic or flammable gases and vapors in ambient air.
Easy to install and operate, the MX 15 control unit combined with the OLC(T) 10 detectors provides a low cost solution for light industrial applications.
Specification
Casing |
|
Size (W x H x D): |
185 x 157 67 cm |
Material: |
ABS |
Mounting: |
By Rail DIN supplied |
Cable entries: |
3 cable-glands M20 (outer diameter 5.5 to 12 mm) |
Protection: |
IP31 |
Power supply |
|
Voltage: |
230 Vac or 115 Vac and 21 Vdc to 30 Vdc (nominal 24 Vdc) |
Consumption: |
20 VA |
Operating temperature: |
-10 to + 45°C |
Cabling |
|
Sensors: |
• 1 flammable gas detector OLC10 or 2 detectors OLC10 TWIN for detection of methane, butane, propane in boiler rooms and LPG, Natural Gas for Vehicles or H2 in car parks |
Maximum cable length: |
• OLC10 (flammable only): 3-wire, shielded, core size 1 to 1.5 mm2, 300 m max |
Display |
|
Type: |
Liquid Crystal Display, 4 digits and extra friendly symbols |
Visual indications: |
4 DELs. Green: power on, Red: alarms triggered, Orange: failure |
Gas and unit: |
Selectable in a programmed list |
Keyboard: |
3 keys for access to main menu, test or acknowledgement |
Alarms & relays: |
• 2 programmable and independent levels, falling or increasing alarms, latching or unlatching modes, local or remote acknowledgment |
Approvals |
|
ATEX 94/9/CE Directive |
category 3G (flammable gas detection metrology EN 61779-1 and EN 61779-4) |
Low Voltage Directive: |
EN 61010 |
Electromagnetic compatibility (EEC directive): |
EN 50270 |